Home           Products           Company           Contact us     
> Fundamentals of Thermodynamics
> Applied Thermodynamics
> Renewable Energies
> Power Engines and Machines
> Internal Combustion Engines
> Refrigeration and Air Conditioning Technology
> Heating and Ventilation in Buildings
> Sanitary Systems
Products  |  Thermal Engineering and HVAC  |  Applied Thermodynamics  |  WL 308
WL 308 Heat Transfer in a Tubular Heat Exchanger Show data sheet (pdf file) Print page
Technical Description

  WL 308 is used to demonstrate the characteristic properties of heat transfer in a tubular heat exchanger. Tubular heat exchangers represent the simplest type of heat exchanger and are the preferred solution for transferring heat with high pressure differences or between high viscosity media (sludge). This type is also used to enable the temperature of the transported medium to be kept constant.
  The experimental unit features a pipe-in-pipe tube as the heat exchanger, a heated tank and pump for the hot water circuit, connections for the cold water circuit, and displays and controls. Hot water in the inner tube and cold water in the outer tube flow either in a parallel flow or in a counterflow. Part of the thermal energy of the hot water is transferred to the cold water. Valves are used to adjust the flow of hot and cold water. The cold water circuit is fed from the laboratory supply.
  The non-linear temperature curve along a heat exchanger can be demonstrated by measuring the inlet and outlet temperatures as well as an additional temperature measuring point half way along the heat exchange path. During this process the water temperature in the inner and outer tubes is measured. Additional measurement of the inner tube wall temperature permits investigation of the heat transfer at the wall.

  In evaluation of the experiment key parameters such as the heat flux and heat transfer coefficient are determined.
  The well-structured instructional material sets out the fundamentals and provides a step-by-step guide through the experiments.

 
Learning Objectives / Experiments
- Heat balances
- Determining the heat transfer coefficient
- Operation in parallel flow and counterflow
- Heat transfer on tube walls and in the flow
- Influence of the mass flow rate on the temperature
  curve
Features
* Operation in parallel flow or counterflow1
* Temperature measuring point on inner tube wall1
* Hot water circuit with temperature controller
Alternative products
WL 110 -- Heat Exchanger Service Unit
WL 302 -- Trainer Tubular Heat Exchanger
WL 315C -- Heat Exchanger Trainer
Specification
[1] Heat transfer in a tubular heat exchanger
[2] Hot water circuit with tank, heater, temperature controller and pump
[3] Cold water circuit from laboratory supply
[4] Temperature controller controls the water inlet temperature for the hot water circuit
[5] Parallel flow and counterflow operation adjustable
[6] Flow rates adjustable using valves
[7] 7 temperature sensors with digital display and selector for temperature measuring points
[8] Process schematic
 
Technical Data

Heat exchanger

- tubes made of Cu, conductivity: 384W/mK

- length: 600mm

- mean transfer area: 0,013m
- tube diameters (t=1mm): D=8mm, D=15mm 
 

Pump
- max. flow rate: 4m/h
- max. head: 4m
- power consumption: 70W
Heater: 3kW, with thermal cut-out
Tank: 6,5L
 
Measuring ranges
- flow meter: 20...250L/h
- temperature: 0...100C
 

Dimensions and Weight
LxWxH: 1060x950x550mm
Weight: approx. 50kg
Required for Operation
230V, 50/60Hz, 1 phase or 230V, 60Hz/CSA, 3 phase
Cold water supply, drain
Scope of Delivery
1 experimental unit
1 set of instructional material
Order Details

060.30800  WL 308  Heat Transfer in a Tubular

                                 Heat Exchanger


Print
© 2005 G.U.N.T. Gerätebau GmbH