ET 405 Heat Pump for Cooling and Heating Operation Show data sheet (pdf file) Print page
Technical Description

  Refrigeration systems and heat pumps only differ in the definition of their use, but can be of the same design. For example, goods can be refrigerated in a supermarket and the store heated with the waste heat. The store can also be cooled with the same system in the summer.
  With ET 405 the cooling and heating operation can be investigated. Different operating modes can be selected via solenoid valves.
  The refrigeration circuit with compressor and condenser (heat exchanger with fan) includes two evaporators with fans (refrigeration stage and freezing stage) and thermostatic expansion valves. The two evaporators can be connected in parallel or in series. For the connection in series the capillary tube serves as expansion element for the refrigeration stage evaporator. The refrigerant circuit is connected to a glycol-water circuit via a coaxial coil heat exchanger. Via solenoid valves the coaxial coil heat exchanger can be switched as an evaporator or condenser. Thus the glycol-water mixture in the tank can be heated or cooled. In pure cooling operation (without heating function) the heat exchanger with fan as  air-cooled condenser dissipates the heat. This heat exchanger can be also switched as an evaporator. 

  The measured values are read from digital displays and can at the same time be transmitted via USB directly to a PC where they can be

analysed using the software included. The software enables a clear representation of the process.  
  The well-structured instructional material sets out the fundamentals and provides a step-by-step guide through the experiments.
   

Learning Objectives / Experiments

- design, operation and key components of a heat

  pump or refrigeration system
- representation of the thermodynamic cycle in

  the log p-h diagram
- comparing different operating modes
- measurement of compressor capacity and heating

  or cooling capacity in the glycol-water circuit
- determination of
  * efficiency
  * coefficient of performance of heat pump and

    refrigeration system
  * specific compressor load
  * compressor pressure ratio
  * specific cooling capacity
  * specific refrigeration capacity
- comparing key figures of heat pump and

  refrigeration system

Features

* Air-to-water heat pump1
* Heating and cooling operation possible1
* High practical relevance by using industrial

  components from refrigeration1
* Different operating modes can be set via

  solenoid valves1
* GUNT software for data acquisition

Alternative products
ET 422 -- Capacity Control and Faults in Refrigeration Systems
Overview
ET 405 Heat Pump for Cooling and Heating
Specification

[1] air-to-water heat pump for cooling or heating operation
[2] different operating modes selectable via solenoid valves
[3] refrigeration circuit with compressor, condenser (heat exchanger with fan), 2 evaporators with fan (refrigeration and freezing stage)
[4] glycol-water circuit with tank, pump and coaxial coil heat exchanger
[5] coaxial coil heat exchanger and heat exchanger with fan can both be used as condenser or evaporator in the refrigeration circuit
[6] 1 thermostatic expansion valve each for all heat exchangers and evaporators
[7] 1 additional evaporation pressure controller and 1 capillary tube for the refrigeration stage evaporator
[8] displays for temperature, pressure, flow rate and power consumption of the compressor
[9] GUNT software for data acquisition with USB under Windows Vista or Windows 7
[10] refrigerant R134a, CFC-free  
 

Technical Data

Compressor
- refrigeration capacity: 934W at -6,7/55C

- power consumption: 620W at -6,7/55C
Heat exchanger with fan
- transfer area: 1,25m, air flow rate: 650m/h 
- capacity: 1148W at DT=15K
Evaporators with fan

- refrigeration stage 
  * transfer area: 1,21m, air flow rate: 80m/h
  * capacity: 140W (tL1=5C, DT1=10K)

- freezing stage 
  * transfer area: 3,62m, air flow rate: 125m/h
  * capacity: 330W (tL1=5C, DT1=10K)
Coaxial coil heat exchanger
- capacity: 1,6kW at 0C; DT=9K
Measuring ranges
- temperature: 11x -50...150C
- pressure: 2x -1...15bar, 1x -1...24bar
- flow rate (refrigerant): 1x 4...40L/h
- flow rate (glycol-water): 1x 2,5...65g/s
- power: 0...1.150W 
 

Dimensions and Weight
LxWxH: 2.210x800x1.900mm
Weight: approx. 330kg
Required for Operation
230V, 50/60Hz, 1  phase or 120V, 60Hz, 1 phase
Water connection
Scope of Delivery

1 trainer

1 GUNT software CD + USB cable

1 set of  instructional material

Order Details

061.40500  ET 405  Heat Pump for Cooling and

                                 Heating Operation